Figure 20:

Option “Two Binary Outputs”
Both binary outputs AB1 resp AB2 switch to high current as soon as the valve position is below resp exceeds the associated

limit value If the binary outputs AB1 resp AB2 are to be inverted (higher current no alarm, lower current alarm), the

association upper/ lower alarm have to be exchanged
Signal range 1 mA resp 5…6 mA, at fault < 50 μA
Option “Binary Inputs”
The binary inputs EB1 and EB2 for two external switches resp sensors initiate the following actions:

2)

EB1

EB2

Action

2)

closed

closed

IN SERVICE

open

closed

Position to be operated

full power to 0%

closed

open

Position to be operated

full power to 100 %

open

open

Hold last value

2)

Factory setting Via communication actions may be turned off or used otherwise EB1 and EB2 can thus also be used as

diagnostics inputs
An input not used is to be short-circuited (wire bridge between + and –)
Attention: Even if opening limit or closing limit are set: these actions are superimposed, and the actuator actually moves to

0 % resp 100%

Built-in Pressure Sensors

The pressure sensors 50 are part of the electronics 40 , therefore, the electronics has to be exchanged for conversion to

this option
Disconnect electric power and air supply Remove cover and electronic unit 40
Remove, if present, the M3 bolts with sealing washers from both chimneys 52 Press in a sealing plug 51 Part No 534 346 013

into the top of each chimney 52 until the collar makes contact DO NOT GREASE!
To install an electronics unit with pressure sensors, carefully guide the tubes 50 of the pressure sensors vertically into the

sealing plugs 51 Do not twist or tilt the unit Fasten screws on the electronics unit