UNPACKING & INSPECTION

Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such

as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment

NOTE:

N

If damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the

carrier A claim for equipment damage in transit is the sole responsibility of the purchaser

Installation and startup of instrument to be carried out only by qualified personnel, familiar with installation and start-up

procedures and operation of this product!

SAFETY INFORMATION

The installation of this product must comply with all applicable federal, state, and local rules, regulations, and codes
Failure to read and follow these instructions can lead to misapplication or misuse of the product, resulting in personal injury

and damage to equipment

Accident Prevention

The connected instrument contains mechanically moved parts, such as feedback levers, which could cause injuries The

operators have to be instructed accordingly

Electrical Safety

• This instrument satisfies the conditions for safety class III, overvoltage category I according to EN 61010-1 or IEC1010-1
• Any work on electrical parts must be done by qualified personnel if any supply is connected to the instrument The

instrument must be used for its designated purpose and connected in accordance with its connection diagram

• Locally applicable installation regulations for electrical equipment must be observed, e g in the Federal Republic of

Germany DIN VDE 0100 resp DIN VDE 0800

• The instrument must be operated with safety extra low voltage SELV or SELV-E
• Safety precautions taken in the instrument may be rendered ineffectual if the instrument is not operated in accordance

with the Master Instructions

• Limitation of power supplies for fire protection must be observed due to EN 61010-1, appendix F or IEC 1010-1

SUMMARY – HART AND 4…20 MA WITHOUT COMMUNICATION

Mounting to Actuator (Valve)

The SRD991 can be mounted to linear or rotary actuators

Connection and Startup

When connecting the supply air and applying a current source to the input terminals, pay attention to polarity An initial

startup required no additional equipment
Use the local push-buttons to change basic parameters such as type of actuator, side of installation, valve opens/closes with

increasing setpoint value, and characteristics curve of the valve (values set ex-factory: stroke actuator, mounting side: left,

valve opens with increasing setpoint value, linear characteristics curve)
Thereafter, an AUTOSTART can be performed during which the SRD991 determines independently the geometric data of the

actuator as well as control parameter, to ensure an optimized operation with the attached valve
HART version:
The positioner can be operated either locally or via handheld terminal or PC (via modem)