Operating modes, Initialize, Device fault – Badger Meter SRD/SRI Valve Positioners User Manual

Page 17: In operation, Failsafe, Out of service, Operating modes 17, Initialize 17 device fault 17, In operation 17 failsafe 17 out of service 17

Advertising
background image

Adjusting and startup of the positioner, as well as the demand for internal information, can be made using the local keys 17

with indication given by LCD, 18 or LEDs

OPERATING MODES

Operation of the positioner is divided into individual operating modes Operating modes may change depending on, for

example, key commands or internal calculations The different operating modes are described in abbreviated form below

Initialize

Upon powerup or reset (pressing the 3 keys simultaneously), several self-tests are conducted Individual steps in the self-test

process are indicated by the LCD or green LEDs
If no error occurs, the device moves to OUT OF SERVICE, if it is still in a delivery condition; AUTOSTART has to be performed If

AUTOSTART was done already, the device will go to IN OPERATION
If faults are detected, the code of the faulty self-test will remain If error occurs again after reset, the device is probably

defective and should be sent in for repair

Device Fault

In the event that the LCD shows a message (or red LED lights up constantly and all green LEDs are off), a device fault is

signaled These faults are detected during cyclical self-test
The device can no longer be operated This could be caused by a jammed menu key or defective program memory
If a device error occurs repeatedly, the device should be sent in for repair

In Operation

After performing an AUTOSTART, the device moves to IN OPERATION and will always, even after restarting or resetting, move

back to the safety position (de-energized valve position) or FAILSAFE If setpoint values are fed via communication, the SRD

will go to IN OPERATION

Failsafe

With FF H1 and Profibus PA Communication
Positioner carries out actions as configured in menu “failure handling” Additionally, the cyclical self-diagnosis takes place
If the instrument is IN OPERATION, but no setpoint values arrive via communication, the SRD will go to FAILSAFE mode, after a

defined time period; either with
• maintaining last value
• output pressureless, or
• with predetermined position
As soon as setpoint values arrive via communication again, the instrument is immediately back IN OPERATION

Out of Service

The SRD991 as delivered is configured to remain OUT OF SERVICE after powerup until moving to IN OPERATION via the

manually initiated function AUTOSTART
In the device state OUT OF SERVICE, the menu entering mode remains active at all times If a device has been IN OPERATION

already and is removed from an actuator and mounted to another, it is recommended to take the device out of operation via

RESET CONFIG (Menu 9 1) prior to disconnecting the device from the first actuator
This enables the next actuator to be started in the delivered condition (see

“Startup”

)

Calibrate

During an AUTOSTART function the device is in condition CALIBRATION The actuator is moved up- and downward several

times, and the device could be busy for a few minutes Subsequently, the device moves to IN OPERATION

Operating Modes

Page 17

August 2014

POS-UM-00010-EN-03