Badger Meter SRD/SRI Valve Positioners User Manual

Page 55

Advertising
background image

SRD991 with HART or without Communication

(With the other versions of the SRD, these menus cannot be selected.)

5.5 Split Range 0 %

-

1

-

1

-

LED1 and LED 3 lights up

LED: The value that was adjusted e.g. with a loop calibrator at the input of
the SRD, is entered with confirmation of keys UP+DOWN as 0 % value.
LCD: By pressing of keys UP or DOWN the value is adjusted and confirmed
with keys UP+DOWN.

5.6 Split Range 100 %

-

-

-

1

1

LED 3 and LED 4 lights up

LED: The value that was adjusted e.g. with an loop calibrator at the input of
the SRD, is entered with confirmation of keys UP+DOWN as 0 % value.
LCD: By pressing of keys UP or DOWN the value is adjusted and confirmed
with keys UP+DOWN.

The keys have Autorepeat: By pressing and holding of a key UP or DOWN, the value is counted
upward, after some time in larger steps.

Example: An input current of 10.4 mA has to correspond to a valve position
of 100 %.

Operation

Page 55

August 2014

POS-UM-00010-EN-03