Fault

Possible Cause

Solution

Unstable behavior,

position control circuit

oscillates

Autostart incomplete,

therefore, control

parameters not suitable

Carry out complete Autostart, see

“Menu 2: Autostart”

Small actuator volume but

high air capacity

Increase damping at pneumatic output, see

“Menu 6: Parameter for Position controller”

reduce gain (P

parameters)

Friction on valve packing

too great

Loosen packing gland slightly or replace

IP module or Pneumatic

amplifier defective

Change module, pneumatic amp

Actuator leakage

Check the actuator and repoint

Actuator reacts too

sluggishly

Air capacity insufficient

Attach booster

Gain set too low

Increase damping at pneumatic output, see

“Menu 6: Parameter for Position controller”

Positioning time T63 set too

high

Reduce positioning time, see

“Menu 6: Parameter for Position controller”

No communication

possible

Input voltage too low

Eliminate voltage drop

Faulty protocol,

communicator and device

type do not match

Check configuration of devices

Wrong electronics unit

Change device

For tuning controller parameters see

“Menu 6: Parameter for Position controller”