Errors detected during self-test, Errors detected during self-test 69 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 69

Advertising
background image

LED Error Codes (with LCD in true text)

LEDs

Description

red

green

M

1

2

3

4

-

1

1

1

1 Micro controller functional test

-

1

1

1

- Micro controller RAM test

-

1

1

-

1 Micro controller ROM test

-

1

1

-

- initialize operating system

-

1

-

1

1 initialize monitor

-

1

-

1

- initialize interfaces

-

1

-

-

1 initialize timer

-

1

-

-

- initialize EEPROM

-

-

1

1

1 initialize data

-

-

1

1

- initialize ADC

-

-

1

-

1 initialize communication

-

-

1

-

- initialize local operation

-

-

-

1

1 start background process

-

-

-

1

- check options and start

-

-

-

-

1 start operating system

1 = LED constant light

LED indication for diagnosis, errors
The following combinations are possible:

After start / reset: (X X X X = error code)
M 1 2 3 4

- X X X X Error detected during Init

s. 11.1

Device in normal operation:
M 1 2 3 4
1 -

-

-

-

Cyclical self-test detects errors

s. 11.2

-

-

-

-

-

diagnosis without LED inform

s. 11.3

¾ x x x x flashing: message

s. 11.4

Errors Detected During Self-Test

During cyclical self-test, certain components of the SRD are under constant surveillance At trouble detection in the

electronics, output y1 becomes pressureless (‘fail safe position’)
If after reset

1)

the display shows the error again, the device is probably defective and should be sent to manufacturer

for repair

LEDs

Description

red

green

M

1

2

3

4

1

-

-

-

-

Red LED lights up const.

RAM / EPROM fault

Actuate “Reset”; send device-

to manufacturer if error re-
appears

1 = LED constant light

1)

Execute reset by simultaneously pressing M+UP+DOWN keys, or by turn-off and restart of input signal

Troubleshooting Guide

Page 69

August 2014

POS-UM-00010-EN-03