SUMMARY – FOUNDATION FIELDBUS

Mounting to Actuator (Valve)

The SRD991 can be mounted to linear or rotary actuators

Connection and Startup

When connecting the supply air and applying a current source to the input terminals, pay attention to polarity An initial

startup required no additional equipment
Use the local push-buttons to change basic parameters such as type of actuator, side of installation, valve opens/closes with

increasing setpoint value, and characteristics curve of the valve (values set ex-factory: stroke actuator, mounting side: left,

valve opens with increasing setpoint value, linear characteristics curve)
Thereafter, an AUTOSTART can be performed during which the SRD991 determines independently the geometric data of the

actuator as well as control parameter, to ensure an optimized operation with the attached valve

Bus Connection

The SRD 991 in the version FOUNDATION Fieldbus is bus compatible, which means that to a 2-core lead, the instruments have

to be attached in parallel according to IEC 1158-2 The lead serves as voltage feeder as well as for digital communication
A FOUNDATION Fieldbus can consist of one or several segments, each with an individual length of up to 1900 meters An

Ex-barrier should not be further than 100 meters from a bus terminal To a segment up to 32 instruments can be attached

A maximum of up to 240 instruments can be addressed (including repeater = connector of segments) To activate each

instrument individually, an individual address has to be entered
From the factory, the address 29h (41) is always stored This address can be changed automatically with the NI-Configurator

System Integration

With the NI-Configurator changes in the configuration of the SRD991 can be carried out The required files (* FFO, * SYM,

* CFF) can be downloaded from the Internet by path

http://www foxboro-eckardt com/products/srd991_en html