Split Range

Split-Range, PV_Scale Splitting

Split Range is useful if an additional control range is demanded

which cannot be covered by one valve only A valve of smaller

nominal size can be applied overtaking the smallest quantities;

a parallel mounted valve of bigger nominal size takes on the

larger quantities
With conventional positioners, this function is realized through

serial connection of the instruments and allocation of individual

regulating ranges (see drawing) With SRD with analog setpoint

value (version HART or “without communication”), this can be

adjusted with menus 5 5 and 5 6
The other versions of the SRD receive the set value via digital

means; the input data signal cannot be split The function

can be realized either in the primary control system, in which

setpoint values are calculated for each valve, or via the variables

PV_SCALE With PV_Scale the digital input setpoint value can be

assigned to the valve span
Example: At low current, only the smaller valve positions; from

approx 40% the large valve is added