P402, Adjustment: 0, P403 – NORD Drivesystems BU0505 User Manual

Page 102: Adjustment: 100

Advertising
background image

SK 54xE – Users Manual for Frequency Inverters

102

BU 0505 GB-1013

P402

[-01]

...

[-06]

Adjustment: 0%

(Analog input adjustment: 0%)

S

-50.00 ... 50.00 V

{ all 0.00 }

This parameter sets the voltage that should correspond with the minimum value of the selected
function for the analog input.

[-01] = Analog input 1: analog input 1, integrated into the FI

[-02] = Analog input 2: analog input 2, integrated into the FI

[-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO

extension

[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO

extension

[-05] = External Analog input 1, 2nd IOE, "External analog input 1 of the 2nd IOE": Analog

input 1 of the second IO extension

[-06] = External Analog input 2, 2nd IOE, "External analog input 2 of the 2nd IOE": Analog

input 2 of the second IO extension

Typical setpoints and corresponding settings:

0 – 10 V

à

0.00 V

2 – 10 V

à

2.00 V (monitored for function 0-10 V)

0 – 20 mA

à

0.00 V (internal resistance approx. 250

W)

4 – 20 mA

à

1.00 V (internal resistance approx. 250

W)

Pos : 184 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P403 – Abgleich Analogei ngang: 100% [SK 54xE] @ 0\ mod_1327681136791_388.doc x @ 9257 @ @ 1

P403

[-01]

...

[-06]

Adjustment: 100%

(Analog input adjustment: 100%)

S

-50.00 ... 50.00 V

{ all 0.00 }

This parameter sets the voltage that should correspond with the maximum value of the selected
function for the analog input.

[-01] = Analog input 1: analog input 1, integrated into the FI

[-02] = Analog input 2: analog input 2, integrated into the FI

[-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO

extension

[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO

extension

[-05] = External Analog input 1, 2nd IOE, "External analog input 1 of the 2nd IOE": Analog

input 1 of the second IO extension

[-06] = External Analog input 2, 2nd IOE, "External analog input 2 of the 2nd IOE": Analog

input 2 of the second IO extension

Typical setpoints and corresponding settings:

0 – 10 V

à

10.00 V

2 – 10 V

à

10.00 V (monitored for function 0-10 V)

0 – 20 mA

à

5.00 V (internal resistance approx. 250

W)

4 – 20 mA

à

5.00 V (internal resistance approx. 250

W)

Pos : 185 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P400 ... P403 @ 0\ mod_1327681197866_388. doc x @ 9280 @ @ 1

Advertising