5 parameters – NORD Drivesystems BU0505 User Manual

Page 109

Advertising
background image

5 Parameters

BU 0505 GB-1013

109

Value Function

Description

Signal

13

PTC input

2

Analog evaluation of signal present. Switching threshold approx. 2.5 V,
Switch-off delay = 2 sec, warning after 1 sec.
NOTE: Fnct. 13 can only be used via DIN 5 up to SK 535E, sizes 1 - 4!
For SK 54xE and sizes above Size 5, there is a separate connection which
cannot be deactivated. If the motor is equipped with a thermistor, for these
devices both terminals must be bridged in order to deactivate the function
(status as delivered).

level

14

Remote control

2, 4

With Bus system control, low level switches the control to control via control
terminals.

High

15

Jog frequency

1

The fixed frequency value can be adjusted using the HIGHER/LOWER and
ENTER keys (P113), if control is via the ControlBox or ParameterBox.

High

16

Motor potentiometer

As in setting 09, however, the frequency is not maintained below the minimum
frequency P104 and above the maximum frequency P105.

Low

17

Para. Set Switchovr. 2

Second Bit of the parameter set switch over, selection of the active parameter
set 1…4 (P100).

High

18

Watchdog

2

Input must see a High flank cyclically (P460), otherwise error E012 will cause a
shutdown. Function starts with the 1st high flank.

0

à1

Flank

19

Setpoint 1 on/off

Analog input switch-on and switch-off 1/2 (high = ON) The low signal sets the
analog input to 0 % which does not lead to shutdown when the minimum
frequency (P104) > than the absolute minimum frequency (P505).

High

20

Setpoint 2 on/off

21

Fixed frequency 5

1

The frequency from P433 is added to the actual setpoint value.

High

22

... 25

reserved POSICON (BU 0510)

26

... 29 impulse functions:

Description below:

30

Disable PID

Switching the PID controller / process controller function on and off (high = ON)

High

31

Disable right running

2

Blocks the >Enable right/left< via a digital Input or bus control. Does not depend
on the actual direction of rotation of the motor (e.g. following negated setpoint).

Low

32

Disable left running

2

Low

33

... 42 impulse functions:

Description below (only SK 500E … 535E).

43

... 44 Speed measurement
with HTL encoder

Description below:

44

3-Wire Direction

(Direction reversal button)

3-Wire-Control, this control function provides an alternative to enable R/L (01,
02), in which a permanently applied level is required.
Here, only a control impulse is required to trigger the function. Control of the FI
can therefore be performed entirely with buttons.
A pulse on the function "Reverse direction of rotation" inverts the present
direction of rotation. This function is reset with a "Stop signal" or by activating a
button for the functions 45, 46, 49.

0

à1

Flank

45

3-W-Ctrl.Start-Right
(Closing button)

0

à1

Flank

46

3-W-Ctrl.Start-Left
(Closing button)

0

à1

Flank

49

3-Wire-Ctrl.Stop
(Opening button)

1

à0

Flank

47

Motorpot.Freq.+

In combination with enable R/L the output frequency can be continuously
varied. To save a current value in P113, both inputs must be at a High voltage
for 0.5 s. This value then applies as the next starting value for the same
direction of rotation (Enable R/L) otherwise start at f

MIN

. Values from other

setpoint sources (e.g. fixed frequencies) are not taken into account.

High

48

Motorpot.Freq.-

High

50

Bit 0 Fixed. freq.Array

Fixed frequency array, binary coded digital inputs to generate up to 32 fixed
frequencies. (P465: -01...-31)

High

51

Bit 1 Fixed. freq.Array

High

52

Bit 2 Fixed. freq.Array

High

53

Bit 3 Fixed. freq.Array

High

54

Bit 4 Fixed. freq.Array

High

55

… 64

reserved POSICON (BU 0510)

65

… 69

Reserved

70

Evacuation runs
SW 1.7 and above

Only for devices with external 24V control voltage (SK 5x5E). There is therefore
also the possibility of operation with a very low link circuit voltage. With this
function the charging relay is activated and the undervoltage and phase error
detection are deactivated.
CAUTION! There is no overload monitoring! (e.g. lifting gear)

High

Advertising