NORD Drivesystems BU0505 User Manual

Page 93

Advertising
background image

5 Parameters

BU 0505 GB-1013

93

P311

Speed controller I

(Speed controller I)

P

0 ... 800 % / ms

{ 20 }

I-component of the encoder (Integration component).

The integration component of the controller enables the complete elimination of any control
deviation. The value indicates how large the setpoint change is per ms. Values that are too small
cause the controller to slow down (reset time is too long).

Pos : 151 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P312 – M omentenstr omregler P @ 0\ mod_1327591805216_388.doc x @ 8580 @ @ 1

P312

Torque current controller P

(Torque current controller P)

S

P

0 ... 800 %

{ 200 }

Current controller for the torque current. The higher the current controller parameters are set, the
more precisely the current setpoint is maintained. Excessively high values in P312 generally lead
to high-frequency oscillations at low speeds; on the other hand, excessively high values in P313
generally produce low frequency oscillations across the whole speed range.

If the value "Zero" is entered in P312 and P313, then the torque current control is switched off. In
this case, only the motor model pre-control is used.

Pos : 152 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P313 – M omentenstr omregler I @ 0\ mod_1327591883202_388.doc x @ 8603 @ @ 1

P313

Torque current controller I

(Torque current controller I)

S

P

0 ... 800 % / ms

{ 125 }

I-proportion of the torque current controller. (See also P312 >Torque current controller P<)

Pos : 153 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P314 – Grenz e M.-s tromregler @ 0\ mod_1327591927202_388. doc x @ 8626 @ @ 1

P314

Torque current controller limit

(Torque current controller limit)

S

P

0 ... 400 V

{ 400 }

Determines the maximum voltage increase of the torque current controller. The higher the value,
the greater the maximum effect that can be exercised by the torque current controller. Excessive
values in P314 can specifically lead to instability during transition to the field weakening zone (see
P320). The values for P314 and P317 should always be set roughly the same, so that the field
and torque current controllers are balanced.

Pos : 154 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P315 – Fel dstr omr egler P @ 1\ mod_1328618593561_388.doc x @ 15410 @ @ 1

P315

Field current controller P

(Field current controller P)

S

P

0 ... 800 %

{ 200 }

Current controller for the field current. The higher the current controller parameters are set, the
more precisely the current setpoint is maintained. Excessively high values for P315 generally lead
to high frequency vibrations at low speeds. On the other hand, excessively high values in P316
generally produce low frequency vibrations across the whole speed range If the value "Zero" is
entered in P315 and P316, then the field current controller is switched off. In this case, only the
motor model pre-control is used.

Pos : 155 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P316 – Fel dstr omr egler I @ 0\ mod_1327592705182_388. doc x @ 8676 @ @ 1

P316

Field current controller I

(Field current controller I)

S

P

0 ... 800 % / ms

{ 125 }

I-proportion of the field current controller. See also P315 >Field current controller P<

Pos : 156 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P300-P399/ Paramet er P317 – Grenz e F elds tromr egler @ 0\ mod_1327592747463_388. doc x @ 8699 @ @ 1

Advertising