P2xx control/characteristic curve parameters – NORD Drivesystems BU0505 User Manual
Page 90

SK 54xE – Users Manual for Frequency Inverters
90
BU 0505 GB-1013
P2xx
Control/characteristic curve parameters
NOTE:
"typical"
P211
P210
P204
P201
P216
P215
Output
voltage
Output frequency
Time
Settings for the...
Current vector control (factory setting)
P201 to P209 = Motor data
P210 = 100%
P211 = 100%
P212 = 100%
P213 = 100%
P214 = 0%
P215 = no significance
P216 = no significance
Linear V/f characteristic curve
P201 to P209 = Motor data
P210 = 100% (static boost)
P211 = 0%
P212 = 0%
P213 = no significance
P214 = no significance
P215 = 0% (boost precontrol)
P216 = 0s (time dyn. boost)