NORD Drivesystems BU0505 User Manual

Page 143

Advertising
background image

5 Parameters

BU 0505 GB-1013

143

P730

Field

(Field)

0 ... 100 %

Displays the actual field in the motor calculated by the FI. The basis for calculation are the motor
data P201...P209.

Pos : 358 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P731 – Akt ueller Par ameters atz @ 0\ mod_1328173520271_388. doc x @ 13054 @ @ 1

P731

Parameter set

(Actual parameter set)

0 ... 3

Shows the actual operating parameter set.

0 = Parameter set 1

1 = Parameter set 2

2 = Parameter set 3

3 = Parameter set 4

Pos : 359 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P732 – Str om Phas e U @ 0\ mod_1328173601208_388. doc x @ 13077 @ @ 1

P732

Phase U current

(U phase current)

S

0.0 ... 999.9 A

Displays the actual U phase current.

NOTE:

This value can deviate somewhat from the value in P719, due to the measurement

procedure used, even with symmetrical output currents.

Pos : 360 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P733 – Str om Phas e V @ 0\mod_1328173830046_388. doc x @ 13100 @ @ 1

P733

Phase V current

(V phase current)

S

0.0 ... 999.9 A

Displays the actual V phase current.

NOTE:

This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.

Pos : 361 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P734 – Str om Phas e W @ 0\ mod_1328173871579_388.doc x @ 13123 @ @ 1

P734

Phase W current

(W phase current)

S

0.0 ... 999.9 A

Displays the actual W phase current.

NOTE:

This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.

Pos : 363 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P735 – Dr ehzahl Dr ehgeber [ SK 54xE] @ 0\ mod_1328173990708_388.doc x @ 13169 @ @ 1

P735

[-01]

...

[-03]

Speed encoder

(Speed encoder)

S

-9999 ... 9999 rpm

Displays the actual rotation speed supplied by the incremental encoder. P301 / P462 / P605 must
be correctly set according to the type of encoder.

[-01] = Speed encoder 1, TTL encoder

[-02] = Speed encoder 2, HTL encoder

[-03] = Speed, absolute encoder, reserved for HTL encoder

Pos : 364 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P736 – Z wischenkreiss pannung @ 0\ mod_1328174969216_388.doc x @ 13192 @ @ 1

P736

D.c. link voltage

(DC link voltage)

0 ... 1000 V DC

Displays the actual link voltage.

Pos : 365 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P737 – Akt uelle Auslas tung Br ems wi derst and @ 0\ mod_1328175007763_388. doc x @ 13215 @ @ 1

Advertising