Terminal block x14 – universal encoder interface, 11 colour and contact assignments for encoders, Colour and contact assignments for encoders – NORD Drivesystems BU0505 User Manual

Page 59: 2 assembly and installation

Advertising
background image

2 Assembly and installation

BU 0505 GB-1013

59

Terminal block X14 – Universal encoder interface

Relevance

SK 540E

SK 545E

Terminals X14:

66

65

64

63

DAT-

DAT+

CLK-

CLK+

Name

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

66

Signal DAT-

(RS485 DAT-)

TTL, RS422

For the connection of SSI, BISS, EnDat
and Hiperface encoders.

P300,

(P604,

however only

for

POSICON)

65

Signal DAT+

(RS485 DAT+)

64

Signal CLK-

For the connection of SSI, BISS and
EnDat encoders.

63

Signal CLK+

Pos : 78 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 5 Elektrischer Ansc hluss St euert eil- Klemmenbl oc k X15 – M ot or PTC und 24V i nput [ SK 54xE] @ 2\ mod_1355475594559_388. doc x @ 52330 @ 5 @ 1

Terminal block X15 – motor PTC and 24V input (above size 8)

Relevance

SK 540E

SK 545E

Terminals X15:

38

39

44

40

T1

T2

VI 24V

GND

Name

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

38

Thermistor input +

EN 60947-8
On: >3.6 kΩ
Off: < 1.65 kΩ
Measurement voltage 5 V
at R <

4 kΩ

The function cannot be switched off, set
a jumper if no PTC is present.

39

Thermistor input -

44

Voltage supply input

24V … 30V

min. 3000mA

Voltage supply for the FI control unit. Is
essential for the function of the
frequency inverter.

40

Reference potential
for digital signals

GND/0V

Reference potential

Pos : 79 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 11 F arb- und Kontaktbel egung für Dr ehg eber [ BU 0500] @ 0\ mod_1325865982124_388. doc x @ 6147 @ 2 @ 1

2.11 Colour and contact assignments for encoders

The incremental encoder connection is an input for a type with two tracks and TTL-compatible signals
for EIA RS 422-compliant drivers. The maximum current consumption of incremental encoders must
not exceed 150 mA.

The pulse number per rotation can be between 500 and 8192 increments. This is set with the normal scaling via parameter
P301 "Incremental encoder pulse number" in the menu group "Control parameters". For cable lengths > 20 m and motor speeds
above 1500 rpm the encoder should not have more than 2048 pulses/revolution.