SK 54xE – Users Manual for Frequency Inverters

152

BU 0505 GB-1013

10.7

undefined provision of the output voltages due to an
error in the reference voltage generation

Short-circuit in analog output

10.8

Option error

External module communication failure

Connection fault / error in the external module

Brief interruption (<1sec) of the 24 V supply of the
internal CAN/CANopen bus

10.9

Module missing / P120

The module entered in parameter (P120) is not available.

Check connections

Pos : 409 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E011 [ SK 180E ... SK 5xxE] @ 2\ mod_1347453318765_388.doc x @ 46626 @ @ 1

E011

11.0

Customer interface

Error in analog-digital converter

Internal customer unit (internal data bus) faulty or
damaged by radio radiation (EMC)

Check control terminals connection for short-circuit.

Minimize EMC interference by laying control and
power cables separately.

Earth the devices and shields well.

Pos : 410 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E012 [ SK 5xxE] @ 2\ mod_1361524186547_388. doc x @ 59066 @ @ 1

E012

12.0

External watchdog

The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.

Check connections

Check P460 setting

12.1

Motor limit

"Motor switch-off limit"

The motor switch-off limit P534 [-01] has triggered.

Reduce load on motor

Set higher value in (P534 [-01]).

12.2

Generator limit

"Generator switch-off limit"

The generator switch-off limit P534 [-02] has triggered.

Reduce load on motor

Set higher value in (P534 [-02]).

12.5

Load limit

Switch-off due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).

Adjust load.

Change limit values ((P525) ... (P527)).

Increase delay time (P528).

Change monitoring mode (P529).

12.8

Analog In minimum

Switch-off due to undershooting of the 0% adjustment value
(P402) with setting (P401) "0-10V with switch-off on error 1"
or "....2"

12.9

Analog In maximum

Switch-off due to overshooting of the 100% adjustment
value (P402) with setting (P401) "0-10V with switch-off on
error 1" or "....2"