5 parameters, P416 ramp time pi setpoint, P417 – NORD Drivesystems BU0505 User Manual

Page 105: Analog output offset

Advertising
background image

5 Parameters

BU 0505 GB-1013

105

P416

Ramp time PI setpoint

(Ramp time PI setpoint value)

S

P

0.00 ... 99.99s

{ 2.00 }

This parameter is only effective when the function PID actual frequency is selected.

Ramp for PI setpoint

Fig.: Flow diagram for PID controller

Pos : 201 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P417 – Of fset Analog ausg ang [SK 54xE] @ 0\ mod_1327940454544_388. doc x @ 9651 @ @ 1

P417

[-01]

...

[-03]

Analog output offset

(Analog output offset)

S

P

-10.0 ... 10.0 V

{ all 0.0 }

[-01] = Analog output: analog output integrated into the FI

[-02] = First IOE, "External analog output of first IOE": Analog output 1 of the first IO

extension

[-03] = Second IOE, "External analog output of second IOE": Analog output 1 of the second

IO extension

In the analog output function an offset can be entered to simplify the processing of the analog
signal in other equipment.

If the analog output has been programmed with a digital function, then the difference between the
switch-on point and the switch-off point can be set in this parameter (hysteresis).

Pos : 203 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P400-P499/ Paramet er P418 – Funkti on Analogausgang [ SK 54xE] @ 0\ mod_1327940583880_388. doc x @ 9697 @ @ 1

PID controller

P413 (P-component)

P414 ( I-component)

P415 (D-component)

Frequency ramp

P102, P103

Ramp setpoint

P416

Maximum frequency P105

(monitored, limited)

Maximum frequency P105

(unlimited)

Minimum frequency P104

(monitored, limited)

- Maximum frequency P105

(unlimited)

Maximum

frequency P105

Minimum

frequency P104

Maximum frequency

auxiliary setpoint P410

Minimum frequency

auxiliary setpoint P411

Analog input 1

Analog input 2

Bus setpoint 3

Bus setpoint 2

Auxiliary

setpoint sources

PotentiometerBox

P400-P404

Scaling

P405-P409

Scaling

Analog input 1

Analog input 2

Bus setpoint 1,2,3

Main

setpoint sources

Fixed frequency 1-5

Controlbox /

PotentiometerBox

Jog frequency

P400-P404

Scaling

P405-P409

Scaling

Also in

combination, se e

se tpoint adjustme nt