P550 back up data record, P551 drive profile – NORD Drivesystems BU0505 User Manual

Page 134

Advertising
background image

SK 54xE – Users Manual for Frequency Inverters

134

BU 0505 GB-1013

P550

Back up data record

(Back up data record)

0 ... 3

{ 0 }

Within the optional ControlBox it is possible to save a data set (parameter set 1 … 4) of the
connected FI. This is saved in a non-volatile memory within the Box, and can therefore be
transferred for other SK 5xxE units with the same database version (see P742).

0 = No change

1 = FI

à ControlBox, the dataset is written from the connected FI to the ControlBox.

2 = ControlBox

à FI, the dataset is written from the ControlBox to the connected FI.

3 = FI

ßà ControlBox, the FI dataset is exchanged with the ControlBox dataset. With this

variant, no data is lost. It is continuously exchangeable.

NOTE:

If parameterisation from old FI's need to be loaded into FIs with new software (P707),
then the ControlBox must previously be written to by the new FI (P550 = 1). The
dataset to be copied from the old FI can then be read out and copied to the new FI.

Pos : 314 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P551 – Antriebs profil @ 0\ mod_1328098517139_388. doc x @ 12054 @ @ 1

P551

Drive profile

(Drive profile)

S

0 … 1

{ 0 }

According to the option the relevant process data profiles can be activated with this parameter.

Note

Activation of profiles

This parameter is only effective for pluggable technology modules (SK TU3-…).

System

CANopen

DeviceNet

InterBus

Technology module

SK TUx-CAO

SK TUx-DEV

SK TUx-IBS

Setting

0 = OFF =

USS protocol (Profile "Nord")

1 = ON =

DS402 profile

AC Drives profile

Drivecom profile