2.1.2.3 Connection to inverter

A shielded signal cable should be used for the data cable between the ParameterBox and the inverter. The power
supply to the ParameterBox must be between +4.5V and +30V.

Please use the following connections to connect the ParameterBox with the corresponding inverter. The
connections apply for fixed connection to the particular inverter via the terminal bar. However, these must always
be compared with the labelling on the ParameterBox.

Description

vector mc

RS485

vector

(CT / VT)

SK 300E

SK 52xE and

higher

X7:

SK 700E / SK 750E

(with option…)

SK CU1-STD

SK CU1-USS

+5V / +15V

15

-

42

42

42

42

GND

16

-

40

40

40

40

P+ (A), RS485 +

17

21

73

73

73

73

P- (B), RS485 -

18

22

74

74

74

74

ATTENTION

Damage to the RS485

Each further frequency inverter which is to be operated simultaneously on the bus cable is only connected in
parallel to the cables RS485+ and RS485-.

Under no circumstances may the power supplies of the frequency inverters (5V) be connected to each other.


For the following series of devices the RS485 data connection is also possible via the RJ12 plug socket which is
integrated into the inverter.

Description

SK 2xxE

Integrated

6-pin RJ12

socket

SK 300E

Integrated
4-pin M12

connector

SK 5xxE

Integrated

6-pin RJ12

socket

SK 700E

>22KW

Integrated

6-pin RJ12

socket

SK 700E

≤22KW

(with option

…-

RS2)

Integrated

6-pin RJ12

socket

SK 750E

Integrated
4-pin M12

connector

+5V

6 ("24V")

2

6

6

(6)

*

2

GND

3

1

3

3

(3)

*

1

P+ (A)

(RS485 +)

1

4

1

1

1

4

P- (B)

(RS485 -)

2

3

2

2

2

3

* For inverters SK700E up to 22KW with the opti

on …-RS2 an external power supply (+4.5V - + 30V) must be provided for the ParameterBox.


In order to connect the ParameterBox to the RJ12 socket of the frequency inverter, a standard RJ12 (6-pole) patch
cable with a length of up to 3 m can be used.
As standard, the 4-pin M12 connector (plug) is available for connection of the ParameterBox to a decentralised
frequency inverter (SK 300E/ SK750E).
If the ParameterBox is supplied from an external power source (+4.5 to +30V) according to the voltage, the data
cables can also be considerably longer.

ATTENTION

Voltage level of external supply

In order to avoid damage, if an external power supply to the ParameterBox is used, care must be taken that the
output voltage of this external source is higher than that of the inverter voltage (however, max. 30V DC).

(E.g.: SK520E: 5V internal supply

→ External supply for the ParameterBox >5V!)