NORD Drivesystems BU0040 User Manual

Page 38

Advertising
background image

NORDAC Control and Parameter Boxes

38

Subject to technical alterations

BU 0040 GB-0113

Parameter

Setting value / Description / Note

P1306

Box password

0 ... 9999

[ 0 ]

If the password function is to be reset, the password selected in the >Set Password< parameter
must be entered here. If the correct password has been selected, than all functions of the
ParameterBox can be used again.

NOTE: In case the password is not known and parameterisation of the inverter needs to be
carried out, please contact our Technical Support.

P1307

Reset Box parameter

Start, Off

[Off]

In this parameter the ParameterBox can be reset to the default setting. All ParameterBox settings
and the data in the storage media will be deleted.

P1308

NORDAC p-box

Version ...

R …

[ … ]

Displays the software version of the ParameterBox. Please keep to hand.


2.2.3

Table of possible error messages


The following describes all possible error messages of the ParameterBox. Error messages which relate to the
connected frequency inverter (E xx.x) are described in the frequency inverter manual or one of the relevant
supplementary instructions.

Display

Error number

Fault

Text in the ParameterBox

Cause

Remedy

Communication error

200

Illegal parameter number

These error messages are due to EMC interference or differing software
versions of the participants.

Check the software version of the ParameterBox and that of the
connected frequency inverter.

Check the cabling of all components, regarding possible EMC
interference

Plug-in EEPROM on the frequency inverter (Memory module)
not recognised (Error: 201) Check for firm connection

201

Parameter value cannot be changed

202

Parameter value out of range

203

Faulty SUB Index

204

No Array parameter

205

Incorrect parameter type

206

Incorrect response identifier
USS interface

207

Checksum error of
USS interface

Communication between frequency inverter and ParameterBox is faulty
(EMC), safe operation cannot be guaranteed.

Check the connection to the frequency inverter. Use a shielded
cable between the devices. Route the BUS leads separately from
the motor cables.

208

Incorrect status identifier
USS interface

Communication between frequency inverter and ParameterBox is faulty
(EMC), safe operation cannot be guaranteed.

Check the connection to the frequency inverter.
Use a shielded cable between the devices. Route the BUS leads
separately from the motor cables.

209

Inverter not responding

The ParameterBox is waiting for a response from the connected frequency
inverter. The waiting time has elapsed without a response being received.

Check the connection to the frequency inverter.
The settings of the USS parameters for the frequency inverter
were changed during operation.