NORDAC Control and Parameter Boxes

48

Subject to technical alterations

BU 0040 GB-0113

P1

P2


Connections

Connection to the horizontal terminal bar is by means of a
4-wire cable.




Settings on the frequency inverter

Name

Parameter number

Value

Notes

Function, digital output 1

P434 [-01]

{00} or {07}*

Setting {07} corresponds to the default value

* Other settings are not permissible and result in the loss of communication between the Simple Setpoint Box and the frequency inverter in IO-C mode.


Information

Deactivation of the IO functions

In "IO-C" mode, the parameterised functions of the IOs "Digital Input 1 (parameter (P420[-01])) and "Digital
Output 1" (parameter (P434[-01])) are deactivated. The condition for this is that Digital Output 1 is parameterised
either to "No function" {00} or the default setting "Fault" {07}.

The DIP switch S1:

3 … 5 of the frequency inverter ("BUS" / "IO") must be left in the factory setting ("OFF" or"0")

in order to prevent communication faults on the frequency inverter.

Information

Parameter P434[-01]

– Disabling the IO-C mode

If the parameter (P434[-

01]) is set to values ≠ {00} or ≠ {07}, the IO-C mode of the SK SSX-3A is barred when the

frequency inverter restarts.

Boot UP display

After switching on, the lettering briefly appears in the display


Operation

Control of the Simple Setpoint Box SK SSX-3A in this mode is identical to that of the SimpleBox SK CSX-3H/ -3E
(see Section 2.2).

Control commands (enable/stop/direction of rotation) and setpoints from the box are only recognised by the
frequency inverter if it has not been enabled from other sources (e.g. digital input of the FI) (priority switching). This
also means that the drive of the source from which it was started must also be set back to Stop.

24V

GND/0V

44

40

B1

C1

24V voltage supply from SK 2xxE

b)

I/O connection for FI setpoint values

IN

OUT

Connection for IO-C mode

SK SSX-3A

SK 2xxE-

44

40

21

1

I/O connection for actual FI values

a) If available on the frequency inverter
b) Supply via terminal 43 or 44, according to the device 24V

DC

– Supply by separate mains unit is also possible

c) Observe correct voltage (24V

DC

), if necessary, provide the supply voltage to the SK SSX3A separately.

44

24V

DC

40

GND

B1

Signal OUT

C1

Signal IN