NORD Drivesystems BU0040 User Manual

Page 17

Advertising
background image

2 Parameter Boxes

– Installation

BU 0040 GB-0113

Subject to technical alterations

17

2.1.4.3 Mechanical installation in a control panel

For installation in the control cabinet door or the control panel, a cut-out of 109mm x 64mm (tolerance +/- 1mm)
must be made. The sealed unit must be inserted in the pre-processed cabinet panel. For attachment to the inside
of the control panel, 6 threaded pins (M4 x 16 mm) (approx. 7 mm projection in installed condition) and the
corresponding nuts are provided. The ParameterBox is now mounted securely on the control cabinet door and has
maximum protection class IP54 on the front side, if mounted correctly.

Electrical connection of the SK CSX-3E or SK PAR-3E parameterisation boxes is made via the RJ12 socket which
is accessible from the rear. The precise assignment of the terminals can be seen in the following section.



Control cabinet front

Control cabinet interior

Seal

Fastening bolts

6 x M4 x 16mm

(nuts and washers are included)

Seal

Advertising