Software User Guide

117

Automation Tab

Device Name: Name of the serial device. Valid values: ttys1 (RS232), ttys5 (RS485)

Baud Rate: Baud rate for the serial device. Supported baud rates are: 300, 600, 1200, 2400, 4800, 9600, 19200 and 
38400
.

Data Bits: Number of data bits. Supported data bits are and 8.

Parity: Parity for serial device. Supported parities are: none, even, odd, mark and space.

Flow Control: Flow control for serial device. Supported flow controls are: none, hardware, xon/xoff, half duplex, full 
duplex.

Stop Bits: Stop bits for serial device. Supported stop bits are and 2.

Protocol: Protocol being used on serial device. Supported protocols are: DNP3, Modbus Master ASCII, Modbus Mas‐
ter RTU, Modbus Slave ASCII, Modbus Slave RTU, Modbus Master RTU Fwd 
and Modbus ASCII Fwd.

Float Word Order: Controls the swapping of words within floats. Ignored if using Daniel mode. This is needed for con‐
figuring the serial slave application. Supported orders are LSW and MSW.

Long Word Order: Controls the swapping of words within longs. Ignored if using Daniel mode. This is needed for con‐
figuring the serial slave application. Supported orders are LSW and MSW.

Enable Daniel Mode: Use Daniel mode extensions when dealing with longs and floats. This is needed for configuring 
the serial slave application.

Click on the Finish button to populate the Serial Ports Table Properties.

To delete an address, select it in the table and click on the Delete button. To edit an existing rule, select it in the 
table and click on the Edit button.

Click on the “Save” button for changes to be saved without activating the interface until you reboot the unit, the 
“Apply” button will save your settings and apply them immediately. To revert to the previous defaults, click on the 
“Revert” button.

3.6.3

Modbus