Red Lion IndustrialPr 6000 Router User Manual

Page 141

Advertising
background image

Software User Guide

141

Automation Tab

Object 32 ‐ Analog Change Event: This field is activated on both Levels 2 and 2+. It’s used to determine if a DNP point 
will generate events. In case a DNP point generates events (Object 2 Binary Change Events) then it should be associ‐
ated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP Points don't’ 
generate events, this feature should be modified by the user.

Object 33 ‐ Frozen Change Event: This field is activated on both Levels 2 and 2+. It’s used to determine if a DNP point 
will generate events. In case a DNP point generates events (Object 2 Binary Change Events) then it should be associ‐
ated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP Points don't’ 
generate events, this feature should be modified by the user.

Click Finish to enter your exception into the table.

To edit an entry, select the station in the table and click on the edit button. To delete an existing entry, select the 
station in the table and click on the Delete button. 

Click on Store I/O Mapping to save your configuration before moving to the next project. Click on the Object Map‐
ping button to return to the DNP3 Object Mapping Configuration dialog window.

Long Outputs Map I/O:

Configure DNP Points: If option is set to No, then no Long Outputs are mapped as DNP points. If set to Yes, the Highest 
Register Address field is shown ton enter a Highest register Address value.

Highest Register Address (Required): This field is used to show or set the highest register address to map DNP points.

Click on Store I/O Mapping to save your configuration before moving to the next project. Click on the Object Map‐
ping button to return to the DNP3 Object Mapping Configuration dialog window.

Binary Counters Map I/O: This option provides configuration of Mapping Binary Counters I/O’s Reg/Index to 
DNP points for generating events based on configured DeadBand and Class Assignments when the status of any 
Binary Counter I/O’s changes. DeadBand and Class Assignments are applied to all the Reg/Index defined by 
Highest Register Address except Reg/Index entries that are defined in Exception DeadBand and Class Assign‐
ments Table.