Red Lion IndustrialPr 6000 Router User Manual

Page 133

Advertising
background image

Software User Guide

133

Automation Tab

Click on Store I/O Mapping to save your configuration before moving to the next project. Click on the Object Map‐
ping button to return to the DNP3 Object Mapping Configuration dialog window.

Analog Inputs Map I/O: This section provides configuration of Mapping Analog Input I/O’s Reg/Index to DNP 
points for generating events based on configured DeadBand and Class Assignments when the status of any Ana‐
log Input I/O’s changes.

Default DeadBand and Class Assignments are applied to all the Reg/Index defined by Highest Register Address except Reg/
Index entries that are defined in Exception DeadBand and Class Assignments Table.

Configure DNP Points: If option is set to No, then no Analog Inputs are mapped as DNP points. If set to Yes, the High‐
est Register Address field is shown to enter a Highest Register Address value.

Highest Register Address (Required): This field is used to show or set the highest register address to map DNP points. 

Enter Default Deadband Value: Values outside this deadband generate events. The deadband parameter sets how 
even data is generated by your module as a DNP slave device.

For example, the Analog Input deadband being set to a value of 1000 will report all of the points as being class 3 data 
(as set by the “Analog Input Class” parameter being set to 3) and it will generate an event every time an analog input 
changes by a value of 1000 or more. This Analog Input deadband can be set to any value between 0 to 32767 (gener‐
ate an event when the value changes by 32767).

Default Object 31 ‐ Frozen Analog Input: This field is activated on both Levels 2 and 2+. It’s used to determine if a DNP 
point will generate events. In case a DNP point generates events (Object2 Binary Change Events) then it should be 

Advertising
This manual is related to the following products: