Automation Tab

Default Object 32 ‐ Analog Change Event: This field is activated on both Levels 2 and 2+. It’s used to determine if a 
DNP point will generate events. In case a DNP point generates events (Object2 Binary Change Events) then it should be 
associated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP Points 
don’t generate events, this feature should be modified by the user.

Default Object 33 ‐ Frozen Change Event: This field is activated on both Levels 2 and 2+. It’s used to determine if a 
DNP point will generate events. In case a DNP point generates events (Object2 Binary Change Events) then it should be 
associated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP Points 
don’t generate events, this feature should be modified by the user.

Exception DeadBand and Class Assignment Table: The Exception table provides you with the ability to define Reg/
Index ranges that are needed to be configured different than Default DeadBand and Class Assignments.

Example: If the Highest Register Address is set to 10 and Reg/Index 2, 4, 6‐7 are needed to be set for different DeadBand and 
Class Assignments than Default, then the final result for all 10 registers would be as follows:

Reg/Index 0‐1, 3, 5 and 8‐10 will be set to Default DeadBand and Class Assignments.

Reg/Index 2, 4 and 6‐7 will be set to Exception DeadBand and Class Assignments.

Note: The Starting Reg/Index and Ending Reg/Index of Exception table entries for a single Reg/Index such as Reg/Index 2 and 
4 in above example has to be the same address.

Click the Add button and the following dialog window will appear:

Starting Reg/Index (Required): Enter the Starting Register for exception class assignments. The valid ranges are 0 to 
your configured highest register, and must be less than or equal to Ending Register.

Ending Reg/Index (Required): Enter the Ending Register for exception class assignments. The valid ranges are 0 to 
your configured highest register, and must be less than or equal to Starting Register.

Enter DeadBand Value (Required): Values outside this DeadBand generate events.

For example: The Analog Input DeadBand being set to a value of 1000 will report all of the points as being class 3 data (as set 
by the “Analog Input class” parameter being set to 3) and it will generate an event every time an analog input changes by a 
value of 1000 or more. This Analog Input deadband can be set to any value between 0 to 32767 (generate an event when the 
value changes by 32767).