Automation Tab

Configure DNP Points: If option is set to No, then no Binary Counters are mapped as DNP points. If set to Yes, the 
Highest Register Address field is shown to enter a Highest Register Address value.

Highest Register Address (Required): This field is used to show or set the highest register address to map DNP points.

Enter Default DeadBand Value: Values outside this DeadBand generate events. The DeadBand parameter sets how 
event data is generated by your module as a DNP slave device.

For example: The Analog Input DeadBand being set to a value of 1000 will report all of the points as being class 3 data (as set 
by the “Analog Input Class” parameter being set to 3) and it will generate an event every time an analog input changes by a 
value of 1000 or more. This Analog Input deadband can be set to any value between 0 to 32767 (generate an event 

Default Object 21 ‐ Frozen Counter: This field is activated on both Levels 2 and 2+. It’s used to determine if a DNP 
point will generate events. In case a DNP point generates events (Object 2 Binary Change Events) then it should be 
associated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP Points 
don’t generate events, this feature should be modified by the user.

Default Object 22 ‐ Counters Change Event: This field is activated on both Levels 2 and 2+. It’s used to determine if a 
DNP point will generate events. In case a DNP point generates events (Object 2 Binary Change Events) then it should 
be associated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP 
Points don’t generate events, this feature should be modified by the user.

Default Object 23 ‐ Frozen Change Event: This field is activated on both Levels 2 and 2+. It’s used to determine if a 
DNP point will generate events. In case a DNP point generates events (Object 2 Binary Change Events) then it should 
be associated to a class (Class 1, Class 2 or Class 3), otherwise it should be associated to None. By default all DNP 
Points don’t generate events, this feature should be modified by the user.