Automation Tab

Binary Inputs Map I/O: This section provides configuration of Mapping Binary Input I/O’s Reg/Index to DNP 
points for generating events based on configured Class Assignments when the status of any Binary Input I/O’s 
changes.

Default Class Assignments are applied to all the Reg/Index defined by Highest Register Address except Reg/Index entries 
that are defined in Exception Class Assignments Table.

Configure DNP Points: If option is No, then no Binary Inputs is mapped as DNP points.

Highest Register Address (Required): This field is used to show or set the highest register address to map DNP points. 
If Configure DNP Points option is set to Yes, the Highest Register Address field is shown to enter a Highest Register 
Address value.

Default Object 2 ‐ Binary Change Event: This field is activated on both Levels 2 and 2+. It’s used to determine if a DNP 
point will generate events. In case a DNP point generates events (Object2 Binary Change Events) then it should be 
associated to a class (Class 1, 2 or 3), otherwise it should be associated to None. By default all DNP points do not gen‐
erate events, this feature should be modified by the user.

Exception Class Assignment Table: The Exception table provides you with the ability to define Reg/Index ranges that 
are needed to be configured differently than Default Class Assignments.

Example: If the Highest Register Address is set to 10 and Reg/Index 2, 4, 6‐7 are needed to be set for different class assign‐
ments than default, then the final result for all 10 registers would be as follows:

Reg/Index 0‐1, 3, 5 and 8‐10 will be set to Default Class Assignments.

Reg/Index 2, 4 and 6‐7 will be set to Exception Class Assignments.

Note: The order of table entry ranges must be entered from lowest Reg/Index to highest Reg/Index, otherwise the Web UI will 
alert the end user for incorrect range entries. The starting Reg/Index and Ending Reg/Index of Exception table entries for a sin‐
gle Reg/Index such as Reg/Index 2 and 4 in above example has to be the same address. The maximum suggested entries for 
the exception table are 10‐15 entries.