Red Lion IndustrialPr 6000 Router User Manual

Page 123

Advertising
background image

Software User Guide

123

Automation Tab

Table 2 ‐ I/O Types and Limits for write commands

I/O Type

Number of regs supported in I/O transfer

Discrete Input

DI

1968

Discrete Output

DO

1968

Analog Input

AI

123

Analog Output

AO

123

Float Input

FI

61

Float Output

FO

61

Long Input

LI

61

Long Output

LO

61

Table 3 ‐ Valid Type Combinations for READ I/O Xfers

Local Type

Valid Remote Type

DI

DI | DO

DO

DI | DO

AI

AI | AO

AO

AI | AO

FI

FI | FO

FO

FI | FO

LI

LI | LO

LO

LI | LO

Table 4 ‐ Valid Type Combinations for WRITE I/O Xfers

Local Type

Valid Remote Type

DI

DO

DO

DO

AI

AO

AO

AO

FI

FO

FI

FO

LI

LO

LO

LO

Advertising