Software User Guide

122

Automation Tab

READ: Used for reading MODBUS registers from the remote station.

WRITE: Write MODBUS output registers to the remote stations.

WRITE_SINGLE: Write a single MODBUS discrete or analog output register to the remote station. Note: Only an option 
when writing a singe discrete output or single analog output.

Local Type: Local Station I/O type. See Table2 ‐ I/O Types and Limits.

Local Relative Address (Required): First address of the local I/O used for the I/O transfer. Valid values are 1 through a 
value of defined registers configured for specified I/O type. The address ranges are displayed on I/O Transfer screen 
under ‘Display of Modbus Default Slave Addresses’ based on configured local register allocation for specified I/O type.

Remote Type: I/O type on the remote station. See Table2, 3, 4 ‐ I/O Types and Limits.

Note: If modbus WRITE operation is selected, this field should be limited to output register types.

Remote Address: First register address for the remote I/O used for the I/O transfer. Valid values are 1 ‐ 65536.

Number of Registers: Number of registers requested in the I/O transfer. This must be 1, if the WRITE_SINGLE com‐
mand is selected. See Table 2, 3, 4 ‐ I/O Types and Limits.

Note: Number of Registers must be 1, if WRITE_SINGLE command is selected.

Enter Update Interval (ms): Time interval, in milliseconds, for the I/O transfer. The recommended value for this field is 
500ms or higher.

Scan Enable Type: I/O Type used for controlling and I/O transfer using either a discrete input or discrete output regis‐
ter. Valid options are DI or DO or Blank if not used.

Scan Enable Address: The address of the discrete register used to control an I/O transfer. Valid values are 0 through 
number of registers configured for specified I/O type. Blank if not used.

Click on the Finish button to populate the IO Transfer Table Properties. If more stations are needed, click on the 
Add button and enter the required field for each station.

To edit a Remote Station, select the station in the table and click on the edit button. To delete an existing station, 
select the station in the table and click on the Delete button. 

Click on the “Save” button for changes to be saved without activating the interface until you reboot the unit, the 
“Apply” button will save your settings and apply them immediately. To revert to the previous defaults, click on the 
“Revert” button.

Table 1 ‐ I/O Types and Limits for read commands

I/O Type

Number of regs supported in I/O transfer

Discrete Input

DI

2000

Discrete Output

DO

2000

Analog Input

AI

125

Analog Output

AO

125

Float Input

FI

62

Float Output

FO

62

Long Input

LI

62

Long Output

LO

62