SECTION 6 - JLG CONTROL SYSTEM
3121171
– JLG Lift –
6-121
CANBUS LINK FROM THE CHASSIS MODULE LOST
1. Position the Platform/Ground select switch to the
Ground position.
2. Plug the analyzer into the connector inside the
Ground control box.
3. Pull out the Emergency Stop switch.
4. The analyzer screen should read:
5. Press enter twice to reach Logged Help. The screen
will read:
6. Hit ESC to get back to the HELP screen and then
use the arrow button to reach VERSIONS. Hit Enter.