Maximum current draw, Short circuit current rating (sccr), N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 10

Advertising
background image

6

DRd Enclosure Installation Manual

Maximum Current Draw

Short Circuit Current Rating (SCCR)

Type

Phase Type

Maximum
Current Draw

Suggested
Breaker
Rating

DRd6

Single Phase (1Ø)

120A

150A

Three Phase (3Ø)

80A

100A

AX6

Single Phase (1Ø)

120A

1

150A

3

Three Phase (3Ø)

80A

1

100A

3

DRd12

Single Phase (1Ø)

240A

300A

Three Phase (3Ø)

160A

200A

AX12

Single Phase (1Ø)

240A

1

300A

3

Three Phase (3Ø)

160A

1

200A

3

AX12X

Single Phase (1Ø)

480A

2

400A

4

Three Phase (3Ø)

320A

2

400A

3

N o t e :

1

Connected to DRd enclosure with a full complement of 20A modules.

2

Connected to two DRd enclosures with a full complement of 20A modules.

3

Installed in a main circuit breaker model auxiliary enclosure.

4

Wire bending space limits the feed to the AX12X-MCB to 400A maximum. ETC

installs a 100% rated two pole breaker (or two poles from a three pole breaker) in

the AX12X-MCB, for a total deliverable current of 400A in a single phase (split

phase) configuration.

Configuration

SCCR at

100-120v

Ac

SCCR at

240 &

277v Ac

DRd6

22,000A

22,000A

DRd6 with AX6 (MCB)

100,000A

65,000A

DRd12

22,000A

22,000A

DRd12 with AX12 Main Lug

22,000A

22,000A

DRd12 with AX12X (cross-bussed) Main Lug

22,000A

22,000A

DRd12 with AX12 Main Circuit breaker

100,000A

65,000A

DRd12 with AX12X Main Circuit breaker

100,000A

65,000A