Terminate Wiring

31

Fluorescent Load Wiring

3-wire Fluorescent

To control 3-wire fluorescent ballasts, the power circuit in the enclosure must be configured

as a fluorescent module type (D15F, D20F, AD15F, AD20F,HD25F), which is a single

density module, with a 2/3 wire fluorescent dimmer mode assignment. Reference the

related Architectural Control Processor Configuration Manual for instructions on changing

the dimmer mode.

Step 1:

Pull the three wire fluorescent ballast wiring into the DRd enclosure per the wire

entry plan.

Step 2:

Strip 5/8” (16mm) of insulation from the end of each load wire.

Step 3:

Terminate the black switched hot/live wire to the top terminal in its assigned

dimmer lug pair. Insert the wire between the back of the lug and the pressure
plate as shown.

Step 4:

Terminate the dimmed hot/live wire to the bottom terminal in its assigned dimmer

lug pair. Insert the wire between the back of the lug and the pressure plate as

N o t e :

When using D20FB modules, connected to dimmable fluorescent 2-wire ballasts

with integral battery backup, use the same terminations as listed in the 3-wire

Fluorescent instructions.

N o t e :

Even though two lugs are used, the configuration (as found in the Dimmer Setup

menu of the ACP) refers only to the top (odd) number lug.

Connection

Cable Size

Torque

Wire Strip

Length

AWG

mm

2

lbf-in

lbf-ft

N - m

15 - 20 amp

load lugs

14 - 10

2.5 - 6

35

2.9

4.0

5/8” - 16mm

8

10

40

3.3

4.5

6 - 4

16

45

3.8

5.1

Ground bus

14 - 8

2.5 -6

75

6.3

8.5

5/16” - 8mm

6 - 4

10

110

9.2

12.4

Neutral bus

(excluding

230V AC)

14 - 8

2.5 -6

75

6.3

8.5

5/16” - 8mm

6 - 4

10

110

9.2

12.4

Neutral

Disconnect

(230V AC only)

14 - 10

2.5 - 6

35

2.9

4.0

5/8” - 16mm

8

10

40

3.3

4.5

6 - 4

16

45

3.8

5.1

a: Insert the wire on the back side of the lugs.