Ridethru option kit, Install the ridethru option kit, N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 50

Advertising
background image

46

DRd Enclosure Installation Manual

RideThru Option Kit

Install the RideThru Option Kit

The RideThru Option kit provides power for the Architectural Control Processor for a

minimum of 12 seconds during brief power outages or power drop outs. The RideThru

Option board fully charges and is ready for operation within ten minutes of the DRd being

powered.

Step 1:

Align the RideThru Option board to the mounting studs in the bottom of the

enclosure.

Notice the mounting holes on the option board. Two are open ended slots

used to place the board, and the remaining two standard mounting holes

used to secure the board in place.

Align the open ended slots to the studs and rest the other end of the board

on the mounting studs.

Step 2:

Secure the board to the two mounting studs with the screws provided.

N o t e :

A single DRd supports the use of either the Unison RideThru Option or the Unison

BatteryPack Option, but not both in the same enclosure.

W A R N I N G :

Risk of Electric Shock! The Unison RideThru option board retains an

electrical charge even when power to the DRd is off.

2008