Introduction

3

Overview

Unison DRd enclosures are available in 6 or 12 module enclosures and are available for an

input voltage range of 85-300 V AC, 47-63 Hz. Enclosures are pre-wired and supplied with

three phase, 4 wire and ground, main lugs which are easily converted for split phase, 3 wire

and ground, operation without the need for additional materials.

DRd enclosures are available in 12, 24 and 48 circuit configurations.

DRd enclosures are supplied pre-wired for the specified voltage for your installation. All

enclosures operate at specified voltages within a frequency range of 47-63 Hz. Phases

within the enclosure may be bused together provided the maximum supplied current does

not exceed that of a three phase connection.

100 / 200 V AC, 47-63 Hz, 1Ø

100 / 173 V AC, 47-63 Hz, 3Ø

120 / 208 V AC, 47-63 Hz, 3Ø

120 / 240 V AC, 47-63 Hz, 1Ø

127 / 220 V AC, 47-63 Hz, 3Ø

230 / 400 V AC, 47-63 Hz, 3Ø CE with Neutral Disconnect

240 / 415 V AC, 47-63 Hz, 3Ø

277 / 480 V AC, 47-63 Hz, 3Ø

Supports universal dimmer modules, fluorescent dimmer modules, constant circuit
breaker modules, relay modules, and reverse phase dimmer modules. Reference

“Modules Specification” , page 57

for a complete list of compatible modules.

The DRd is controlled from either the Echo

®

Architectural Control Processor

(E-ACP), SmartLink

®

Architectural Control Processor (S-ACP) or the Paradigm™

Architectural Control Processor (P-ACP).

N o t e :

In 48-circuit configurations, two DRd12-24 enclosures are cross-bussed to an

AX12X series main lug or main circuit breaker auxiliary enclosure. A single

Architectural Control Processor (Echo, Paradigm, or SmartLink ACP) provides

control for both enclosures.