DRd Enclosure Installation Manual

Step 5:

Terminate the Neutral as described in the following section, dependant on your

DRd enclosure model.

Non Neutral Disconnect

For enclosures which have neutral jumpers fitted, the Neutral of the load, fed by the

Emergency module, must be connected to the Neutral terminal of an adjacent module.

Neutral Disconnect

In enclosures without neutral jumpers (Neutral Disconnect enclosures), the Neutral of the

load should not be connected to another load’s Neutral terminal. This can cause unwanted

tripping of RCD modules.

Instead, an auxiliary neutral terminal must be fitted to the neutral plate and the loads should

be connected to the terminal. If your enclosure was ordered with Emergency modules from

the factory, the auxiliary neutral terminal will be factory fitted. If you require an auxiliary

neutral terminal for field installation, please contact ETC as shown using the details in

Contacting ETC, page 2

.

Figure 2: Emergency Module Connections

Constant live

line is landed

on the Neutral

lugs

Dimmed or

switched line is

landed on live

lugs