Mounting auxiliary and drd enclosures together – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 19

Advertising
background image

2

Install Enclosures

15

Mounting Auxiliary and DRd Enclosures Together

Unison DRd and AX auxiliary enclosures are designed to be surface mounted on load

bearing walls in an electrical closet or a room with restricted public access. One DRd

enclosure may be bussed to the AX series auxiliary enclosure, which may contain a main

circuit breaker or a main lug for power distribution to the adjacent DRd12 enclosure. Two

DRd12 enclosures may be cross-bussed to an AX12X auxiliary enclosure which is

designed to provide main lug or main breaker input feed termination to the adjacent DRd12

enclosures.

The wall must be strong enough to hold all enclosures fully populated with modules, conduit

and wire. Reference

“Where to Install the Enclosure,” page 7

for weight, dimension and

clearance requirements.

Step 1:

Determine where the enclosures will be installed using the weight and dimension

requirements detailed in

“Where to Install the Enclosure,” page 7

.

Step 2:

Use the measured slot dimensions located in the graphics below to mark the hole

locations for the mounting hardware.

Step 3:

Drill the holes and install the mounting hardware for each enclosure.

• Four 3/8” (M8-M10) bolts or screws 2-4” (50-100mm) long, and suitable

wall plugs are suggested mounting hardware per enclosure (lag bolts

recommended).

• Both the surface and the mounting hardware must support the weight of

the enclosures fully populated with modules.

• Expose at least 1” (25mm) of threads for mounting the enclosure.

Step 4:

Remove the conduit knockouts from the mating side conduit plugs on the DRd

and auxiliary enclosures before installation. Only remove the knockouts that are

adjacent to another enclosure.

Step 5:

Install one DRd enclosure first (follow instructions as outlined in

“Mounting

Individual Enclosures on a Wall,” on page 13

. Remember to install the DRd

enclosure to either side of the auxiliary enclosure in cross-bussed applications.

Step 6:

Align the auxiliary enclosure against the DRd enclosure and mount it to the

previously installed hardware. Keyholes in the DRd and auxiliary enclosures are

aligned with each other for mounting to Unistrut or Kindorf. With conduit holes

mated, the bolt spacings are on 16” (406mm) centers (top left DRd and top left

432mm

17”

451mm

17.75”

194mm

7.64”

113mm

4.45”

160mm

6.3”

432mm

17”

62mm

2.44”

787mm

31”

406mm

16”

406mm

16”

330mm

13”

559mm

22”

559mm

22”

DRd12-48 rear panel view