Drd right i/o data terminations, Auxiliary power, N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 38

Advertising
background image

34

DRd Enclosure Installation Manual

.

DRd Right I/O Data Terminations

Auxiliary Power

The auxiliary power connector (labeled Aux Power) provides termination for up to 16 wires

in the eight position pluggable connector. Each terminal allows up to two 16 AWG (1.5mm

2

)

wires and provides 24vDC power to control stations when used with the Paradigm Station

Power Module. Auxiliary power is not compatible with the Echo or SmartLink Station Power

Module.

Step 1:

Pull control auxiliary power wiring (typically 16 AWG (1.5mm

2

) red / black wire

pair) into the enclosure through the conduit opening previously prepared.

Step 2:

Strip 3/16” (5mm) of insulation from the ends of each wire pair.

Step 3:

Remove the auxiliary power connector from the right I/O board.

Step 4:

Loosen the terminal screws for as many auxiliary wire pairs as you are

terminating.

Step 5:

Insert the black auxiliary power wire from the pair into a “-” terminal on the

connector and tighten the screw to secure the wire into the connector.

Step 6:

Insert the red auxiliary power wire from the pair into a “+” terminal on the

connector and tighten the screw to secure the wire into the connector.

Step 7:

Repeat steps 5 and 6 for each auxiliary power wire pair.

Step 8:

Replace the connector on the right I/O board.

N o t e :

A DRd enclosure supports the use of either the Unison RideThru option or the

Unison BatteryPack option, but not both.

W A R N I N G :

RISK OF DEATH BY ELECTRIC SHOCK! Failure to disconnect all power to

the enclosure before working inside the DRd could result in serious injury

or death.
De-energize main feed to DRd enclosure and follow appropriate Lockout/

Tagout procedures as described in NFPA Standard 70E. It is important to

note that electrical equipment such as dimmer enclosures can present an

arc flash safety hazard if improperly serviced. This is due to available large

short circuit currents on the feeders of the equipment. Any work on

energized equipment must comply with OSHA Electrical Safe Working

Practices.

N o t e :

All low voltage control cables must run in separate conduit from power wires.

N o t e :

It is required that you terminate LinkConnect / EchoConnect station wiring and the

auxiliary power wiring in the same enclosure (rack 1) where the station power

module and architectural control processor will be installed.

S

IGNAL

D

ISTRO

R

IDE

T

HRU

/B

AT

T

J9

DUAL

RACKS

LPS

APM

DMXB

AUX POWER

LON LINK / ECHO BUS

CDI

DMXA

B

+

B

-

COM

A

+

A

-

COM

7183B4606

REV

F

© 2013

ETC

,

INC

.

MADE

IN

THE

U

.

S

.

A

.

B

+

B

-

COM

COM

PANIC

A

+

A

-

COM

DMXB DMXA

SRC

OFF

END

DMX P

ASS

-T

HRU

Advertising