Control specifications, N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 13

Advertising
background image

1

Prepare for Installation

9

Control Specifications

The riser below is typical of a small Unison system utilizing Echo Architectural Control

Processors (E-ACP) for control and Unison Echo

®

Inspire™ control stations for control

activation. DMX input to the DRd enclosures provide an additional level of system control

and integrates the architectural and theatrical lighting control systems.

N o t e :

Split phase applications require a simple field adjustment to the phase bussing.

See “Modify Phase Bus for 120V AC Split Phase Operation” on page 19.

Wire Access

Location

Wire Size

Feed (max)

350 Kcmil

185mm

2

DRd6 Feed

(max)

250 KCmil

120mm

2

Load Wires

12 - 6AWG

2.5 - 16mm

2

Control Wires

Top

acceptable

acceptable

acceptable

acceptable

Bottom

acceptable

acceptable

acceptable

preferred

Left side

Do Not Use

Do Not Use

acceptable

acceptable

Right side

Do Not Use

Do Not Use

acceptable

acceptable

Wire Access

Location

Wire Size

DRd12 Feed

(max) 250 Kcmil

120mm

2

DRd6 Feed

(max)

2/0-3

70mm

2

Load Wires

12 - 6AWG

2.5 - 16mm

2

Control Wires

Top

acceptable

acceptable

acceptable

acceptable

Bottom

acceptable

acceptable

acceptable

preferred

Left side

Do Not Use

Do Not Use

acceptable

acceptable

Right side

Do Not Use

Do Not Use

acceptable

acceptable

N o t e :

DRd enclosures are shipped with the lugs installed in a top feed orientation by

default. You can change the lug orientation to a bottom feed if required.

To additional

DRd rack

enclosures

EchoConnect

& DMX

power

feed

power

feed

power

feed

To load circuits

DMX input
to DRd rack

ETC Console

(for optional stage lighting)

EchoConnect

Preset 4

Unison DRd12
rack enclosure

Echo

Relay Panel

Unison DRd12
rack enclosure

Echo Inspire Stations

Element

console

Advertising