Connect line power wiring – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 29

Advertising
background image

4

Terminate Wiring

25

Connect Line Power Wiring

Connect Line Feed in an Individual DRd Installation

Line feed cables are terminated on the main phase lugs. It is best to route line (feeder)

cables first, load neutral and ground/earth wires next, load phase and control wires last. In

multiple enclosure installations, load neutral and ground/earth wires must terminate in the

same enclosure as the matching load phase wires.

The bus bars are different for each enclosure type (DRd6 or DRd12) and each voltage (120,

230 or 240-277). Graphics are provided on the following page for reference.
Step 1:

Pull the line phase, neutral and ground cables to the enclosure through the

openings (conduit or other fittings) previously prepared.

Step 2:

Strip the insulation from the end of each cable and terminate them to the lugs.

Reference the table below for wire stripping lengths.

• Line and neutral connections are labeled L1, L2, L3 and N. The equipment

grounding/earthing lug is labeled with the universal grounding symbol for

easy identification.

W A R N I N G :

All terminations must be done with the power off. DRd enclosures installed

without an accessible power disconnect device cannot be serviced or

operated safely. In some instances, this device may be an auxiliary

enclosure with a main circuit breaker. Follow all local codes and

restrictions.
Before servicing, de-energize main feed to DRd and follow appropriate

Lockout/Tagout procedures as described in NFPA Standard 70E. It is

important to note that electrical equipment such as dimmer enclosures can

present an arc flash safety hazard if improperly serviced. This is due to

available large short circuit currents on the feeders of the equipment. Any

work on energized equipment must comply with OSHA Electrical Safe

Working Practices.

C A U T I O N :

Line and load wires used with the Unison DRd must be copper. Do not use

aluminum wire.

N o t e :

For DRd6 and DRd12 main lug, main breaker, and cross-bussed applications,

reference the

Unison Auxiliary Series Enclosure Installation Manual

.

Model

Hex Key Size / Wire Strip Length

Phase

Strip

Length

Neutral

Strip

Length

Ground/

Earth

Strip

Length

DRd6 120, 240, 277V AC

3/16” /

5mm

5/8” /

16mm

3/16” /

5mm

5/8” /

16mm

3/16” /

5mm

5/8” /

16mm

DRd6 230V AC

5/16” /

8mm

1” / 25mm

5/16” /

8mm

1” / 25mm

3/16” /

5mm

5/8” /

16mm

DRd12 240, 277V AC

5/16” /

8mm

1” / 25mm

3/8” /

10mm

1” / 25mm

3/16” /

5mm

5/8” /

16mm

DRd12 120, 230V AC

3/8” /

10mm

1” / 25mm

3/8” /

10mm

1” / 25mm

3/16” /

5mm

5/8” /

16mm