4

Terminate Wiring

29

Step 1:

Route the load wires to the DRd enclosure(s) through the conduit previously

installed.

Step 2:

Prepare the load wires for termination:
a: Label each wire in the set with circuit designation.
b: Separate load circuit wires into ground, neutral and hot/live wire bundles.

Step 3:

Strip 5/8” (16mm) of insulation from the end of each load wire.

Step 4:

Route each load hot/live wire to its individual load output connection.

N o t e :

Plan load wiring appropriately to avoid splicing wiring. Only one load wire per load

terminal.

C A U T I O N :

Dress and terminate wires neatly and avoid leaving extra wire inside the

enclosure. Too much clutter (especially along the right side of the enclosure) can

restrict air circulation and reduce cooling efficiency. If cabling interferes with

airflow during operation, the DRd may be forced to shut down due to overheating.
Load wires should not cross between DRd enclosures. Instead, they should enter

the enclosure in which they will be terminated. Hot/Live and neutral load wiring

must follow the same conduit/path for each circuit.

Connection

Cable Size

Torque

Wire Strip

Length

AWG

mm

2

lbf-in

lbf-ft

N - m

15 - 20 amp

load lugs

14 - 10

2.5 - 6

35

2.9

4.0

5/8” - 16mm

8

10

40

3.3

4.5

6 - 4

16

45

3.8

5.1

Ground bus

14 - 8

2.5 - 6

75

6.3

8.5

5/16” - 8mm

6 - 4

16

110

9.2

12.4

Neutral bus

(excluding

230V AC)

14 - 8

2.5 - 6

75

6.3

8.5

5/16” - 8mm

6 - 4

16

110

9.2

12.4

Neutral

Disconnect

(230V AC only)

14 - 10

2.5 - 6

35

2.9

4.0

5/8” - 16mm

8

10

40

3.3

4.5

6 - 4

16

45

3.8

5.1

a: Insert the wire on the back side of the lugs.
b: Torque the lug screw to the recommended

value indicated in the table below.