DRd Enclosure Installation Manual

Step 3:

Tighten the lugs to the correct torque based on cable size. Torque ratings are

also labeled in the DRd enclosure for your convenience.

100, 120, 127 V AC, 3Ø DRd Enclosures

N o t e :

CE enclosures are supplied with ANSI hex wrenches for line feed terminations.

Type

DRd12

120 and 230V AC

DRd12

240 and 277V AC

DRd6

(all models)

Lug Mounting

Bolt Torque

6 Ft-lbs

8 Nm

11 Ft-lbs

15 Nm

6 Ft-lbs

8 Nm

Wire Range

350kcmil -

1 AWG

2-6 AWG

250kcmil -

1 AWG

2-6 AWG

2/0-3 AWG

4-6 AWG

185mm

2

-

50mm

2

35mm

2

-

16mm

2

120mm

2

-

50mm

2

35mm

2

-

16mm

2

70mm

2

-

25mm

2

25mm

2

-

16mm

2

Lug Wire

Tightening

Torque

375 in-lbs

200 in-lbs

375 in-lbs

275 in-lbs

50 in-lbs

45 in-lbs

42.4 Nm

22.6 Nm

42.4 Nm

31 Nm

5.65 Nm

5.1 Nm

C A U T I O N :

Dress wires neatly and avoid leaving extra wire inside the enclosure. Too much

clutter can restrict airflow and cause overtemp errors.

N o t e :

For 120V AC single phase installation you must modify the phase bus before

connecting wiring.

See “Modify Phase Bus for 120V AC Split Phase Operation” on

page 19.