Dmx control wiring, Ax12x cross-bussed interconnection, N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 40

Advertising
background image

36

DRd Enclosure Installation Manual

DMX Control Wiring

DMX wire preparation and termination will vary with the type of wire and termination kit

being used. Please refer to the instructions supplied with the DMX termination kit for

specific wire preparation.

DMX Input Wire Termination using the Screw Terminals

Connector

The graphic to the left illustrates DMX termination layout for the

screw-terminal connectors that are intended for use with Belden

9729 cable (or approved equal) cable type.

Screw terminal connectors are supplied as standard in the DMX

Preparation Kit w/ Screw Connector, part number 4100A1012.

Be aware that cable other than Belden 9729 may have a different

color code for its wire pairs.

DMX Input Wire Termination using the Insulation

Displacement Connector (IDC)

The graphic below illustrates DMX termination layout for an insulation displacement

connector. This connector type is intended for use with Belden 1583A (or approved equal,

such as Category 5, 5E, or 6) cable type. Be aware that cable other than Category 5 may

have a different color code for its wire pairs.

Reference and follow the DMX Cable Preparation for IDC Termination instruction sheet that

is shipped with the insulation displacement pluggable connector kit (part number

4100A1013).

AX12X Cross-bussed Interconnection

Termination is provided for connection of a second DRd enclosure when installed in a

cross-bussed application. This termination point is labeled “Dual Enclosures” on the right

I/O board.

An interconnect cable is provided which connects enclosure 1, which is the DRd with the

ACP installed, to enclosure 2, which is the secondary enclosure in the cross-bussed

system. This cable is labeled at both ends, one end indicating enclosure 1 and the other

end indicating enclosure 2. You must have installed this cable to the correct enclosure for

proper operation.

This interconnection of enclosures allows full control of both DRd enclosures from only one

Architectural Control Processor installed in rack 1. This may only be used in a cross-bussed

applications.

Reference the Unison Auxiliary Enclosure Installation Manual for instructions to accomplish

this termination.

N o t e :

It is required that you terminate DMX wiring in the same enclosure (rack 1) where

the architectural control processor will be installed.

1

2

3

4

5

6

7

8

COM

n/c

n/c

n/c

n/c

n/c

Data + (Red)

Data - (Black)

From source

DMX A

If daisy-chaining to
another rack or
DMX device...

1

2

3

4

5

6

7

8

n/c

n/c

COM

Data +

Data -

O

RG

W/ORG

W/BRN

COM

Data +

Data -

O

RG

W/ORG

W/BRN

Use the DMX Pass-Thru

connector

If daisy-chaining to

another rack or

DMX device...

DMX A

Thru

DMX B

Thru

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

COM

Data +

Data +

Data -

Data -

O

RG

W/ORG

BRN

GRN

W/GRN

BLU

W/BLU

W/BRN

ORG

W/ORG

BRN

GRN

W/GRN

BLU

W/BLU

W/BRN

COM

From source

DMX A

From source

DMX B