Rough-in Conduit and Wiring

21

Rough-in Conduit to the DRd Enclosure

Line feed wires terminate on the main lugs provided.

The DRd12 enclosure is shipped from the factory with the main lugs in a top feed

orientation. The lugs can be changed to a bottom feed orientation by removing the lug

mounting bolt, rotating the lug 180°, and re-mounting the lug in the opposite lug mounting

PEM. This is true for all DRd12 models.

The DRd6 enclosure phase lugs are both top and bottom feed by default and don’t require

any change, but the neutral and ground lugs will require re-orientation for bottom feed.

When utilizing an auxiliary enclosure with the DRd enclosure, line feed wires from the

auxiliary enclosure enter the DRd enclosure through the top side conduit knockout. For

cross-bussed installations the line feed wires will be fed to the DRd through the conduit

knockout on the adjoining side of the auxiliary enclosure.

Enclosure

Type

DRd12

120 and 230V AC

DRd12

240 and 277V AC

DRd6

(all models)

Lug Mounting

Bolt Torque

6 Ft-lbs

8 Nm

11 Ft-lbs

15 Nm

6 Ft-lbs

8 Nm

Wire Range

350kcmil -

1 AWG

2-6 AWG

250kcmil -

1 AWG

2-6 AWG

2/0-3 AWG

4-6 AWG

185mm

2

-

50mm

2

35mm

2

-

16mm

2

120mm

2

-

50mm

2

35mm

2

-

16mm

2

70mm

2

-

25mm

2

25mm

2

-

16mm

2

Lug Wire

Tightening

Torque

375 in-lbs

200 in-lbs

375 in-lbs

275 in-lbs

50 in-lbs

45 in-lbs

42.4 Nm

22.6 Nm

42.4 Nm

31 Nm

5.65 Nm

5.1 Nm

L1

L2

L3

N

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

L1

L2

L3

N

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

Top Feed DRd

Bottom Feed DRd