Wire fluorescent, N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual

Page 36

Advertising
background image

32

DRd Enclosure Installation Manual

shown in the graphic above. Torque the wire to the recommended value in the

torque table above.

Step 5:

Strip the neutral wire to the length indicated in the table above and terminate to

the neutral terminal assembly. Torque to the recommended value also indicated

in the table above.

Step 6:

Strip the ground/earth wires to the length indicated in the table above and

terminate to the ground bus terminal. Torque to the recommended value also
indicated in the table above.

2-wire Fluorescent

To control 2-wire fluorescent ballasts, the power circuit in the enclosure must be configured

as a standard module type (D15, D20, AD15, AD20, ED15, ED25, HD15, HD25) with a 2/

3 wire fluorescent dimmer mode assignment. Reference the related Architectural Control

Processor Configuration Guide for instruction to change dimmer mode.

Step 1:

Pull fluorescent ballast power wiring into the DRd enclosure per the wire entry

plan.

Step 2:

Strip 5/8” (16mm) of insulation from the end of each load wire.

Step 3:

Terminate the load wire (typically black) to the assigned dimmer lug by inserting

wire between the back of the lug and the pressure plate.
a: Insert the wire on the back side of the lugs.
b: Torque the lug screw to the recommended value indicated in the table below.

Step 4:

Strip the neutral wire to the length indicated in the table above and terminate to

the neutral terminal assembly. Torque to the recommended value also indicated

in the table above.

Step 5:

Strip the ground/earth wires to the length indicated in the table above and

terminate to the ground bus terminal. Torque to the recommended value also

indicated in the table above.

N o t e :

Ground connections must use all metal nuts and lock washers.

Connection

Cable Size

Torque

Wire Strip

Length

AWG

mm

2

lbf-in

lbf-ft

N - m

15 - 20 amp

load lugs

14 - 10

2.5 - 6

35

2.9

4.0

5/8” - 16mm

8

10

40

3.3

4.5

6 - 4

16

45

3.8

5.1

Ground bus

14 - 8

2.5 -6

75

6.3

8.5

5/16” - 8mm

6 - 4

10

110

9.2

12.4

Neutral bus

(excluding

230V AC)

14 - 8

2.5 -6

75

6.3

8.5

5/16” - 8mm

6 - 4

10

110

9.2

12.4

Neutral

Disconnect

(230V AC only)

14 - 10

2.5 - 6

35

2.9

4.0

5/8” - 16mm

8

10

40

3.3

4.5

6 - 4

16

45

3.8

5.1

N o t e :

Ground connections must use all metal nuts and lock washers.