N o t e – ETC Unison DRd Dimming Rack Enclosure User Manual
Page 20
Advertising
16
DRd Enclosure Installation Manual
Ax) for installation convenience.
Step 7:
Install the ETC supplied 2 1/2” (64mm) nylon insulated chase nipple and 2 1/2”
(64mm) locknut between the auxiliary and DRd enclosures.
Step 8:
For cross-bussed DRd12-24 installations, install the second DRd12-24 by
following steps 4 through 7 above.
Step 9:
Check that each enclosure is level and plumb then tighten the mounting
hardware for a secure installation.
N o t e :
Reference the related
Auxiliary Enclosure Installation Manual
to complete the
auxiliary enclosure installation and for DRd12-24 and DRd 12-48 enclosure input
power bus wiring termination.
Follow the instructions in this manual for all other DRd enclosure installation
procedures.