6.5 Voltage supply with communication via

GSM mobile radio connection (standard application)


Note!

In order to be able to communicate with the CSI-F-10 using GSM mobile radio, this
must first be configured. This means that the mobile phone numbers which are
authorized for access must be stored in the CSI-F-10 and appropriate permissions
assigned.
In order to configure the GSM radio module CSI-F-10, first connect with the GSM radio
module CSI-F-10 as previously described (e.g. via CSI-B-2, HMG 510 or CMU 1000).


If the CSI-F-10 GSM radio module is operated with the aid of a PC modem via a GSM
mobile radio connection, communication occurs using a special protocol.

In this case the CSI-F-10 does not have an HSI address, because it is activated via the
special protocol for modem connections and only a point to point connection is possible
in this protocol.

If sensors are connected to the CSI-F-10, the GSM radio module can be transferred to
the pass-through mode. In the pass-through mode, the sensors can be accessed using
the normal HSI addresses "a" ... "z".



For the GSM-Modem for the PC connection, we recommend the following devices:
-

"GS64 Terminal"; Manufacturer: CEP AG (

www.cepag.de

)

- "GPRS GSM Quadband Modem / USB"; Manufacturer: ConiuGo GmbH (www.coniugo.com)




Warning!
If the time of day or date of the GSM radio module is modified via a mobile radio
connection, then the new time is only visible at the next connection setup in CMWIN.
Time of day and date are however changed immediately in the CSI-F-10.

PC

(using

GSM

modem)

GSM Radio

Module

CSI-F-10

( No address )

Sensor (address a)

Sensor (address b)

GSM

HSI