HYDAC CSI-F-10 User Manual

Page 95

Advertising
background image

GSM Radio Module CSI-F-10

Page 95

Status 29.01.2009

HYDAC ELECTRONIC GMBH

Part.-Nr.:

669752

9.4.12 Ramp

The Ramp function is used to prevent rapid value changes. Under
stable conditions, the input value is shown at the output. Changes of
the input value are however not relayed directly to the output, but
only in small steps instead. Like a slope, so to speak. Different
slopes can be defined for positive and negative value modifications
at the same time.

The parameters Falling ramp and Rising ramp are used to specify
the maximum permissible value changes per second.

If for example the value 5 is set for Rising ramp and the input value
jumps from 0 to 100, then the output will be only slowly increased,
and it will take 20 seconds for the output value to reach 100.

Inputs: x:

(Numerical)

Outputs: y: (Numerical)
Parameters: p

1

:

Falling ramp

(Numerical)

p

2

:

Rising ramp

(Numerical)