6 update utility, 7 query measurement, 8 query register – INFICON SQM-242 Thin Film Deposition Controller Card Software Operating Manual User Manual

Page 82: 9 update register

Advertising
background image

5 - 8

IP

N 07

4-

55

1-

P1

A

SQS-242 Operating Manual

5.8.6 Update Utility

@QU;<param1>;<Index>
02

SQM242 Mode (0/1)

03

SQM242 Period

04

SQM242 Filter

06

Front Panel Enabled (0/1)

07

Application Visible (0/1)

08

Full Scale Output (Index=1 to 6)

14

Application On Top(0/1)

5.8.7 Query Measurement

@QM;<param1>
1n

Output n Power (n=1 to 6)

2n

Output n Rate

3n

Output n Thickness

4n

Output n Deviation

5n

Sensor n Rate (n=1 to 8)

6n

Sensor n Thickness

7n

Sensor n Frequency

8n

Sensor n % Life

9n

Analog Input n Voltage

5.8.8 Query Register

@QR;<param1> (returns register value in HEX)
0

Layer/Phase Register

1

Sensor/Output Register

2

Analog/Output Register

20

Source Index Register

21

Source Index Done Register

22

Relay Register

24

Input Register

25

Layer Index Register

26

Layer Index Done Register

5.8.9 Update Register

@UR;<param1>;<value> (value in HEX)
0

Layer/Phase Register

1

Sensor/Output Register

2

Analog/Output Register

20

Source Index Register

21

Source Index Done Register

22

Relay Register

24

Input Register

25

Layer Index Register

26

Layer Index Done Register

XXX

Any Register