12 Appendix

12.1

Technical data

12.1.1

Interfaces

12.1.2

Electrical data

USB device

Connector designation

Setup

Connector type

Mini-B

Number

1

Application

Connection to a PC (setup program)

Max. current

100 mA

System bus Out

Connector designation

Bus Out

Connector type

RJ45

Number

1

Application

Connection of a router module or a multifunction panel

Connection cable

Network cable (patch or crossover cable), at least CAT5 (S/FTP)

Cable length

Up to 100 m

Ethernet

Connector designation

LAN

Connector type

RJ45

Number

1

Application

Communication with PC (setup program, web server), e-mail server,
and Modbus master/slave

Protocol

TCP/IP, HTTP, DHCP, SMTP+POP3, Modbus/TCP

Transfer rate

10 Mbit/s, 100 Mbit/s

RS232 or RS422/485 (serial interfaces)

Depending on the device type

Connector designation

Com1 and Com2

Connector type

D-Sub

Number

2

Application

Fieldbus applications, communication via modem with a PC (setup
program) or with an e-mail server

Protocol

Modbus RTU (master or slave);

PROFIBUS-DP (slave, Com2 only)

Transfer rate

Modbus: 9600 Bd, 19200 Bd, 38400 Bd;

PROFIBUS: max. 12 Mbit/s

Voltage supply

Connection

At the front (removable 2-pole terminal strip with Push-In technol-
ogy)

Voltage

DC 24 V +25/-20 % SELV

Residual ripple

5 %

Current consumption

Max. 350 mA (at DC 19.2 V)

Current consumption of lined-up modules also has to be considered
(see „Hardware configuration“ in the setup program)!

Power consumption

Max. 7 W