5 Operation

34

5.2

System states

The following characteristics indicate the various system states:

"Run" system state

•

To achieve this state, use the system switch (Run) or the setup program;

if there is an error in a mandatory module, the system does not enter the "Run" state.

Requirement: the system must not be in the "Init" state.

•

Input values are adopted by the system; outputs are actuated (are active).

•

Interfaces (Com1 and Com2) are active.

•

The system switch, setup program, or PLC can be used for changeover to "Stop".

•

The setup program can be used to transfer the configuration; here the user can make the
adjustment whether the system is set to the safe "Stop" state beforehand.

•

Software update is possible, but the system is set to "Stop" automatically.

"Stop" system state

•

To achieve this state, use the system switch (Stop), setup program, or PLC.

Requirement: the system must not be in the "Init" state.

•

Input values are adopted by the system; outputs are switched off (inactive).

•

Modules are in safe state (except independent controller modules).

•

Interfaces (Com1 and Com2) are active.

•

The setup program can be used for changeover to "Run", provided this is not prevented by
the "Stop" switch setting.

•

The setup program can be used to transfer the configuration.

•

Recording function continues to run, default values are used in part.

•

Software update is possible.

•

Three-step controller in manual mode: control element can still be operated, provided com-
munication with the multifunction panel is available.

"Init" system state

•

To achieve this state, use the system switch ("Origin" reset).

•

Outputs are switched off (inactive).

•

Modules are in safe state (except independent controller modules).

•

Interfaces (Com1 and Com2) are active.

•

Changeover to "Run" and "Stop" is not possible using the setup program or PLC.

•

System startup must be performed with the setup program.

•

Recording function continues to run; analog inputs of the multifunction panel are set to de-
fault values.

•

PLC program and all internal PLC memory areas are deleted; PLC is set to original state.

"Calibration mode" system state

•

Activation in setup program using the "Calibrate / test" function (online parameter) for the
relevant module

•

The entire system enters calibration mode.

•

PLC in "Stop" state; system bus in "Run" state (outputs are actuated)